Siderise FLGS Foiled Linear Gap Seal
Siderise FLGS (Foiled Linear Gap Seal) is an intumescent based solution designed to seal junctions between building elements to resist the spread of fire and smoke, providing up to 120 minutes of integrity (E120).
Versatile protection for junctions
The design of the Siderise FLGS incorporates layered intumescent and polymeric foam strips wrapped in 100micron Siderise branded foil, providing a range of on-site benefits.
Siderise FLGS Foiled Linear Gap Seals are flexible, water-resistant, intumescent linear gap seals that expand when exposed to heat. They provide a versatile means of sealing junctions between building elements against fire penetration. They are maintenance-free and resistant to fungi and vermin.
The compressible foam core accommodates different joint widths to allow for structural movement whilst providing resistance to fire and smoke.
Standard sizes are available to suit voids up to 20mm and provide up to 2 hours fire resistance (Integrity only).
Siderise FLGS Foiled Linear Gap Seals are made from a compressible and flexible composition with layered intumescent and polymeric foam strips wrapped in 100 micron siderise branded foil.
In fire conditions, the seal maintains a close-fitting position to prevent the passage of smoke. At the designed temperature, the intumescent coating begins to expand on the fire side of the joint.
During this reaction, the foam gradually compresses and is replaced by the expanding mass of intumescent graphite.
The seal retains its flexibility on the non-fire side to accommodate any heat-induced movement of the structural elements. Thus the fire is prevented from penetrating rapidly into the joint.
Table 1: Fire Resistance to BS EN 1366-4:2021
Product Type | Max. Joint Width (mm) | Seal Width (mm) | Seal Depth (mm) | Integrity (E) (mins) |
---|---|---|---|---|
FLGS/FS120/012-012 |
10 |
12 |
12 |
120 |
FLGS/FS120/029-012 |
20 |
29 |
12 |
120 |
Application Technique: Compressed into gap/joint ensuring that the intumescent is correctly oriented parallel to the opposing faces of the void.
Siderise FLGS Foiled Linear Gap Seals are supplied in 1 meter lengths with a width to suit the size of the gap required.
The standard sizes are listed in the Fire Resistance table above. For small voids above 20mm we recommend the use of CW-FS, please consult our technical service team for more installation guidance for this application
- Block/masonry/concrete walls and floors shall be at least 150mm thick and have at least the same fire rating as that of the Linear Gap Seal.
- Block/masonry/concrete gap faces must be within the density range of 450 to 2300kg/m3, and gap faces must be free from loose or flaking material.
Siderise FLGS Foiled Linear Gap Seals environmental properties:
- Halogen-free
- Individual components may be separated mechanically; however, they are currently not recyclable.
The following information is available upon request or via download from the website:
- Material Handling Sheet
For technical advice or support please contact: technical.services@siderise.com
For Installation Training or Site Inspections please contact: site.services@siderise.com
The information in this datasheet is believed to be accurate at the date of publication. Siderise has a policy of continuous product improvement and reserves the right to alter or amend the specifications of products without prior notice. Siderise does not accept responsibility for the consequences of using the products described outside of the recommendations within this datasheet. Expert advice should be sought where there is any doubt about the correct specification or installation of Siderise products.
Acoustic solutions
We have a range of acoustic treatments for buildings and construction sites.
FAQs
Get quick answers to common queries or contact our team for more advice. Your questions answered.
FLGS Foiled Linear Gap Seals are supplied in 1-metre lengths in widths that either suit maximum gap widths of 10mm or 20mm. For wider gaps, please refer to CW-FS Firestop
FLGS Foiled Linear Gap Seal is simply compressed into gap/joint, ensuring that the intumescent is correctly oriented parallel to the opposing faces of the void.
Case Studies
Related projects
Siderise is a market leader in the design and development of specialist passive fire.
Contact us
We're here to help you
Call for our main switchboard
Email us for technical enquiries
Email us for site support
Complete the form for the right response
Augmented Reality
Point your camera at the QR code. Tap the banner that appears on your screen.