CH

Application

Siderise CH horizontal cavity barriers for non-ventilated cladding facades are used to full fill the void between the external envelope and internal structure. They are installed in combination with RV vertical cavity barriers as part of a system.

The construction of CH horizontal cavity barriers offers excellent resistance to the passage of both smoke and fire. Additionally, by fully sealing the void, they assist ventilated façades to function by maintaining air pressurisation compartmentation.

Importantly, their unique stonewool lamella core construction enables the vertical barriers to accommodate the serviceability movement normally associated with rainscreen façades.

Intersections between horizontal and vertical cavity barriers are simply abutted. The leading-edge compresses directly against the external envelope. No intumescent strip is required.

Product Description

Siderise CH horizontal cavity barriers are installed within the cavity formed between the cladding facade and the inner structural wall using appropriate Siderise support brackets. Brackets are available in either galvanised mild steel (G) or stainless steel (S).
 

Siderise CH horizontal cavity barriers for rainscreen cladding applications consist of a non-combustible stone wool lamella core, with reinforced aluminium foil faces, giving an overall reaction to fire performance of Class ’A1’ to EN 13501-1.

Standard sheet sizes are 1200mm x 1100mm.

 

Fire Performance

Product Fire Performance

Siderise CH horizontal cavity barriers have been tested in accordance with EN 1366-4: 2006+A1: 2010. The cavity barriers maintained integrity (E) and insulation (I) requirements for up to 2 hours as detailed in Table 1.

The tests have been undertaken to assess the ability of the cavity barriers to reinstate the fire resistance of a lightweight aerated concrete supporting construction. This is the standard assembly for testing such cavity barrier products as it allows the performance of the individual barrier to be classified.
 

System Fire Performance

Siderise cavity barrier products have been used in a growing number of large-scale system tests such as BS 8414 (1&2) and NFPA 285. These may be used to evaluate the performance of the Siderise cavity barriers within a complete cladding system. The rules for extended application of results from BS 8414 tests are subsequently defined in BS 9414.
 

In all cases, we recommend that the specifier and user review the specific project configuration regarding available large-scale system test data and the latest National Building Regulations, local Building Code and/or government advice.

For information regarding performance and assembly details in system tests please contact the technical team.

Table 1: Fire Resistance to EN 1366-4

Product Ref Void Width (mm) Thickness (mm) Compression (min.) Integrity (Mins) Insulation (mins) Product Length (mm) Bracket Requirement
CH-120/120
20 - 50
120
+5mm
120
120
1200
None.
CH-60/60
20 - 50
90
+5mm
90
60
1200
None.
CH-120/120
51 - 150
120
+10mm
120
120
1200
2no. B65/110
CH-60/60
51 - 150
90
+10mm
90
60
1200
2no. B65/110
CH-120/120
151 - 250
120
+10mm
120
120
1200
2no. B195
CH-60/60
151 - 250
90
+10mm
90
60
1200
2no. B195
CH-120/120
251 - 300
120
+10mm
120
120
1200
2no. B355
CH-60/60
251 - 300
90
+10mm
90
60
1200
2no. B355

Please note:

  • Support brackets should be installed at 600mm fixing centres (300mm from each end).
  • The brackets are supplied as standard in 1mm galvanised mild steel (G) or stainless steel (S), in a flat form for site folding. They incorporate pre-notched indents to aid this process.
  • Lengths of the barrier are secured with these dedicated brackets, which impale the product at mid thickness to a depth of 75% of void.
  • The brackets are drilled on-site and secured to the inner structural wall using non-combustible steel anchors or screws. These fixings are not supplied by Siderise.
  • Please see separate installation instructions available on our website.
Thermal Performance

Thermal conductivity: λ= 0.038 W/m.K (tested foil to foil)

Technical Specification

Table 2: Product Properties

Properties Value
Form Supplied Sheets : 1200mm x 1200mm (UK and EU); 1200mm x 1100mm (RoW): Thickness is denoted by the rating
Pre-cut strips : 1200mm x (cavity + compression) x thickness, please see Tables 1
Product Finish Aluminium foil to surfaces exposed to cavity
Density Nominal 75 kg/m3
Thermal Conductivity λ = 0.038 W/m.K (tested foil to foil)
Void Sizes 20mm to 300mm - please see table 1
Reaction to Fire Classified A1 to EN 13501-1
Resistance to Fire Please see Table 1
CH-120/120 cavity barriers are manufactured from CW-FS120
CH-60/60 cavity barriers are manufactured from CW-FS60
CW-FS is certified under Certifire CF 563 and Intertek WHI19-32944301.
Environmental

Stone wool core is recyclable

Additional Information Available

The following information is available upon request or via download from the website:

  • Standard Details
  • Safety Data Sheet 
  • Installation Instructions
Technical Support

Technical Services Team: technical.services@siderise.com

Site Services Support

Siderise offers a range of services to contractors and installers. These include toolbox product installation and site installation inspection and reporting (subject to availability and by agreement).

Site Services Team: site.services@siderise.com

Context

The information in this datasheet is believed to be accurate at the date of publication. Siderise has a policy of continuous product improvement and reserves the right to alter or amend the specifications of products without prior notice. Siderise does not accept responsibility for the consequences of using the products described outside of the recommendations within this datasheet. Expert advice should be sought where there is any doubt about the correct specification or installation of Siderise products.